InteliLite 9 Global Guide
318
Related FW 1.1.0 Related applications AMF, MRS
Comm object 9
Description
Output closes when any BOC alarm appears.
The output opens, if:
No BOC alarm is active and
Fault reset button is pressed
AL Common BOC
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 6
Description
Output closes when any sensor fail alarm appears.
The output opens, if:
No sensor fail alarm is active and
Fault reset button is pressed
AL Common Fls
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 4
Description
Output closes when any shutdown alarm appears.
The output opens, if:
No shutdown alarm is active and
Fault reset button is pressed
AL Common Sd
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 3
Description
Output closes when any warning alarm appears.
The output opens, if:
No warning alarm is active and
Fault reset button is pressed
AL Common Wrn
6 back to Logical binary outputs alphabetically