InteliLite 9 Global Guide
380
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 196)
Generator <> Frequency Delay (page 196)
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Oil Pressure
Alarm evaluated Gen-set is running
Related applications AMF, MRS
Description
This alarm indicates that the oil pressure is lover than the pressure set in Oil
Pressure Sd (page 180) setpoint.
Sd Oil Pressure
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
Overload BOC (page 192) adjusts the overload limit.
Overload Delay (page 192) adjusts the delay
Sd Overload
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Overspeed
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs immediately when the engine speed has exceeded the limit. The
behavior of the overspeed alarm is adjusted by the following setpoints:
Overspeed Sd (page 178) adjust the overspeed limit
Overspeed Overshot (page 179) adjust the additional overspeed limit
Overspeed Overshot Period (page 179) adjust the time period of additional
overspeed limit
Sd Overspeed
6 back to List of alarms level 2