Related FW 1.1.0 Related applications AMF, MRS
Comm object 9997
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 34. Limits for this protection are adjusted by setpoints
Analog Protection 3 Wrn (page 210) and Analog Protection 3 Sd (page 211). Delay is adjusted by setpoint
Analog Protection 3 Delay (page 211).
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Protection types
Note: This parameter has to be adjusted via InteliConfig.
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Alarm
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Note: This parameter has to be adjusted via InteliConfig.
AIN Prot03