InteliLite 9 Global Guide
371
Alarm Type Other
Alarmlist message Module(slotA) - fake module
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm indicates that false module is inserted in slot.
Module(slotA) - false module
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message Module(slotA) - unexpected
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that in slot is inserted different module than which is
configured or the module is unconfigured and has to be configured for proper
function.
Module(slotA) - unexpected
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message Module(slotA) - unknown module
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm indicates that unknown module is inserted in slot.
Module(slotA) - unknown module
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Fuel Transfer Failed
Alarm evaluated When FUEL PUMP (PAGE 327) is active
Related applications AMF, MRS
Description
This alarm will occur when there is no increase of fuel level when FUEL PUMP
(PAGE 327) is active.
Wrn Fuel Transfer Failed
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Transferring Fuel
Alarm evaluated When FUEL PUMP (PAGE 327) is active
Related applications AMF, MRS
Description This alarm will occur when FUEL PUMP (PAGE 327) is active.
Wrn Transferring Fuel
6 back to List of alarms level 1