Setpoint group Engine settings Related FW 1.1.0
Range [units]
0 .. Fuel Pump Off (page 163) [%]
Default value 20 % Alternative config NO
Step 1 %
Comm object 10100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Visible only if the logical binary output FUEL PUMP (PAGE 327) is configured and
logical binary input FUEL PUMP ON/OFF (PAGE 306) isn’t configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 327) on.
Image 8.3 Fuel Pump On
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 306) is configured then binary
output FUEL PUMP (PAGE 327) is control by this binary input. Setpoints Fuel Pump On and
Fuel Pump Off (page 163) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 327) is configured.