InteliLite 9 Global Guide
198
Subgroup: Voltage Protection
Setpoint group Protections Related FW 1.1.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15668 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Generator <> Voltage protection. GCBclosing is blocked, if
the protection is disabled!
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Generator
Overvoltage Sd (page 193), Generator Overvoltage Wrn (page 194), Generator
Undervoltage BOC (page 194), Generator Undervoltage Wrn (page 194) and Generator
<> Voltage Delay (page 195).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 310).
Generator <> Voltage Protection
6 back to List of setpoints
Subgroup: Frequency Protection
Setpoint group Protections Related FW 1.1.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15670 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Generator Frequency protection. GCBclosing is blocked, if
the protection is disabled!.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Generator
Overfrequency BOC (page 195), Generator Overfrequency Wrn (page 195), Generator
Underfrequency BOC (page 196), Generator Underfrequency Wrn (page 196), and
Generator <> Frequency Delay (page 196).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 310).
Generator Frequency Protection
6 back to List of setpoints