InteliLite 9 Global Guide
204
Setpoint group AMF settings Related FW 1.1.0
Range [units]
50 .. Mains Overfrequency (page 203) [%]
Default value 98,0 % Alternative config NO
Step
1,0 % of Nominal Frequency (page 150)
Comm object 8312 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Threshold for mains underfrequency.
Mains Underfrequency
6 back to List of setpoints
Setpoint group AMF settings Related FW 1.1.0
Range [units] 0,0 .. 600,0 [s]
Default value 0,5 s Alternative config NO
Step 0,1 s
Comm object 8311 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Delay for Mains Underfrequency (page 204) and Mains Overfrequency (page 203) protection.
Mains < > Frequency Delay
6 back to List of setpoints
Subgroup: AMF Settings
Setpoint group AMF settings Related FW 1.1.0
Fixed value Auto
Description
Setpoint adjust the behavior of closing MCB when the mains returns.
Manual When Return From Island = MANUAL and there is a Mains Fail, gen-set is started and
take the load. After mains return the load have to manually transfer to mains. Also in
Alarmlist will be displayed Manual Restore (page 370) alarm.
Note: Select MANUAL in case you need to manually control the moment when the
load is transferred back to the mains.
Auto No automatic mode change is performed.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
Return From Island
6 back to List of setpoints