InteliLite 9 Global Guide
242
Setpoint group Basic settings Related FW 1.1.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1 A
Comm object 12049 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is current limit for generator current protections and means maximal continuous generator current. Nominal
Current can be different from generator rated current value.
Note: This value is used when any other alternate configuration is not active.
Nominal Current 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.1.0
Range [units] Monophase / Splitphase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12058 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
Generator winding connection system
Connection Type 1