InteliLite 9 Global Guide
295
LBI: A
Related FW 1.1.0 Related applications AMF, MRS
Comm object 859
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the second set (setpoints with number 2).
Alternate Config 2
6 back to Logical binary inputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 860
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the third set (setpoints with number 3).
Alternate Config 3
6 back to Logical binary inputs alphabetically
Related FW 1.1.0 Related applications AMF
Comm object 692
Description
This binary input can switch controller function between AMF and MRS.
Note: Binary input “AMF function has higher priority than the setpoint Operation Mode (page 154) in
Basic settings.
AMF Function
6 back to Logical binary inputs alphabetically
Related FW 1.1.0 Related applications AMF
Comm object 211
Description
This binary input can allow or block the AMF start. In case of running gen-set in AUTO mode gen-set goes to
cooling procedure and stops.
AMF Start Block
6 back to Logical binary inputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 9 and is the answer not in the manual?

ComAp InteliLite 9 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 9
CategoryController
LanguageEnglish

Related product manuals