4-35
4-3 Wiring Conforming to EMC Directives
4
System Design
Noise Filters for the Power Supply Input
Use the following noise filters for the Servo Drive's power supply.
Dimensions
SUP-EK5-ER-6 3SUP-HQ10-ER-6
Servo Drive model
Noise filter for the power supply Input
Model
Rated
current
Max. leakage
current (60 Hz)
Manufacturer
R88D-GTA5L
SUP-EK5-ER-6 5 A
1 mA
(at 250 VAC)
Okaya Electric
Industries Co.,
Ltd.
R88D-GT01L
R88D-GT02L
R88D-GT04L 3SUP-HQ10-ER-6 10 A
3.5 mA
(at 500 VAC)
R88D-GT01H
SUP-EK5-ER-6 5 A
1 mA
(at 250 VAC)
R88D-GT02H
R88D-GT04H
R88D-GT08H 3SUP-HQ10-ER-6 10 A
3.5 mA
(at 500 VAC)
R88D-GT10H
3SUP-HU30-ER-6 30 A
3.5 mA
(at 500 VAC)
R88D-GT15H
R88D-GT20H
R88D-GT30H
3SUP-HL50-ER-6B 50 A
8 mA
(at 500 VAC)
R88D-GT50H
R88D-GT75H
105
115
5.5
43
70
52
10
95
M4
M3
M4
Ground
terminal
Cover mounting
screw
Cover
Noise Filte
r
50.0
60.0
12.0
10.0
11.6
13.0
75.07.0
2.0
88.0
100±2.0 53.1±2.0
5.0
Two, 4.5 × 6.75 dia. Two, 4.5 dia.
Six, M4