7-19
7-4 Disabling the Automatic Gain Adjustment Function
7
Adjustment Functions
7-4 Disabling the Automatic Gain
Adjustment Function
This section provides precautions for disabling realtime autotuning and the adaptive filter. These
functions are enabled by default.
Disabling Realtime Autotuning
By setting the Realtime Autotuning Mode Selection (Pn21) to 0, the automatic estimation of the
Inertia Ratio (Pn20) will stop, and realtime autotuning will be disabled.
However, the estimated Inertia Ratio (Pn20) will remain. If the Pn20 value is obviously incorrect,
perform normal mode autotuning or calculate and set the appropriate value manually.
• When disabling the automatic adjustment function, the RUN Command
Input (RUN) must be turned OFF.
• To enable the Realtime Autotuning Mode Selection (Pn21), turn OFF the
RUN Command Input (RUN), and then turn it back ON.
Precautions
for Correct Use
Precautions
for Correct Use