EasyManuals Logo
Home>Omron>Controller>R88D-GT series

Omron R88D-GT series User Manual

Omron R88D-GT series
510 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #352 background imageLoading...
Page #352 background image
5-65
5-16 User Parameters
5
Operating Functions
• Use this parameter to set the Servomotor’s allowable operating range for the position command
input range.
• An overrun limit error (alarm code 34) will occur if the setting is exceeded.
• The function will be disabled if the setting is 0.
• For details, refer to Overrun Limit on page 5-19.
Explanation of Settings
• The instantaneous speed observer can both increase the responsiveness and reduce vibration at
stopping by improving the speed detection accuracy for devices with high rigidity.
• The Inertia Ratio (Pn20) must be set correctly.
• The Instantaneous Speed Observer Setting (Pn27) will be 0 (disabled) if the Realtime Autotuning
Mode Selection (Pn21) is not set to 0 (enabled).
• Use this parameter to set the notch frequency of notch filter 2 for resonance suppression.
• The notch filter will be disabled if the setting is 1500.
• Use this parameter to set the notch width of notch filter 2 for resonance suppression.
• Increasing the setting will increase the notch width. Normally, use the default setting.
• Use this parameter to set the notch depth of notch filter 2 for resonance suppression.
• Increasing the setting will decrease the notch depth and the phase lag.
• Use this parameter to set vibration frequency 1 for damping control to suppress vibration at the
end of the load.
• Measure the frequency at the end of the load and make the setting in units of 0.1 Hz.
• Setting frequency: 10.0 to 200.0 Hz. The function will be disabled if the setting is 0 to 9.9 Hz.
• Refer to Damping Control on page 7-35 for more information.
Pn26
Overrun Limit Setting
Setting range 0 to 1000 Unit 0.1 revolution Default setting 10
Power OFF→ON
---
Pn27
Instantaneous Speed Observer Setting
Setting range 0 to 1 Unit --- Default setting 0
Power OFF→ON
---
Setting Explanation
0 Disabled
1 Enabled
Pn28
Notch Filter 2 Frequency
Setting range 100 to 1500 Unit Hz Default setting 1500
Power OFF→ON
---
Pn29
Notch Filter 2 Width
Setting range 0 to 4 Unit --- Default setting 2
Power OFF→ON
---
Pn2A
Notch Filter 2 Depth
Setting range 0 to 99 Unit --- Default setting 0
Power OFF→ON
---
Pn2B
Vibration Frequency 1
Setting range 0 to 2000 Unit 0.1 Hz Default setting 0
Power OFF→ON
---
Position
Position
Speed
All modes
All modes
All modes
Position

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron R88D-GT series and is the answer not in the manual?

Omron R88D-GT series Specifications

General IconGeneral
BrandOmron
ModelR88D-GT series
CategoryController
LanguageEnglish

Related product manuals