6. Function blocks
6.1 Manufacturer function blocks
Figure 106: Year time switch parameters tab with and example in which a year range is being selected
Setting time range parameters
If + Call enabled is selected for the function block under Function block dia-
gram/Parameters/, it will be possible to change the switching times in the PARAMETER
menu on the device while in RUN / STOP mode.
Time ranges are defined by setting an ON and an OFF time.
The contact therefore always switches from ON to OFF, as shown in the following →
"HY - Year time switch (Hora Year)", page 178.
Please note:
The year time switch only operates correctly if you observe the following
rules:
l The On year must be before the Off year,
l ON and OFF times, the same time parameters must be defined.
Examples of correct time parameter configurations:
l ON = --/--/Year, OFF = --/--/Year,
l ON = --/Month/Year, OFF = --/Month/Year,
l ON = Day/Month/Year, OFF = Day/Month/Year
Setting time range parameters in which the on phase is from the beginning of the
year to the end of the year (whole year(s)):
Channel A
ON: -- -- 22, OFF: -- -- 30 means:
The year time switch should switch on at 00:00 on day 01.01.2022 and switch off when
the OFF year has elapsed at 00:00 on day 01.01.2031. The parameters are set in one
channel. Refer to the → "HY - Year time switch (Hora Year)", page 178 below for this
time range.
Setting time range parameters in which the on phase is from the beginning of the
month to the end of the month (whole month(s)):
First channel ON: -- 04 --, OFF: -- 10 -- means:
182