9. easyE4 inside
9.4 Time behavior of the inputs and outputs
9.4.1.2 Delay time with DEBOUNCE deactivated
When DEBOUNCE is deactivated, the typical delay time for DC signals on the input for
easyE4 base devices caused by the hardware lies between 0.025ms and 0.25ms (A).
Figure 240: Switching behavior with DEBOUNCE deactivated
Typical delay times with DEBOUNCE deactivated are:
l On-delay for:
l I1 to I4 easyE4 default: 0.025 ms
l I1 to I4 EASY806-DC-SWD: 0.02 ms
l I5 to I12: 0.25 ms
l Off delay for:
l I1 to I4 easyE4 default: 0.025 ms
l I1 to I4: 0.02 ms
l I5, to I8: 0.4 ms
When using high-speed counter function blocks, the delay time
for the input signals must not exceed 0.025ms. DEBOUNCE
must therefore be deactivated.
When DEBOUNCE is deactivated ensure that input signals are
free of noise. The easyE4 device responds to very short sig-
nals.
To allow reliable recognition and processing of the input signal,
it must be applied stably for a certain duration, the length of
which depends on the circuit diagram processing cycle time.
508
easyE4 11/18 MN050009 EN www.eaton.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton easyE4 series and is the answer not in the manual?

Eaton easyE4 series Specifications

General IconGeneral
BrandEaton
ModeleasyE4 series
CategoryRelays
LanguageEnglish

Related product manuals