Procedure
Proceed as follows to change the delay time:
1. Call the settings of the SITOP software, for example, by right-clicking the SITOP UPS icon
in the information area and then selecting "Configuration".
2. In the "SITOP DC UPS Configuration" dialog box, enter the wait time in seconds as a
command line parameter in the "Floating operation" tab:
Syntax: <Path>\USVShutdown.bat -<Time in seconds>
Example: C:\Program Files (x86)\Siemens\MotionControl\siemens
\sinumerik\hmi\base\USVShutdown.bat -180
Figure 4-1 SITOP Monitor Floating operation
3. Confirm the setting with "Save".
4.15.3.2 Configuring SITOP UPS Manager (Ethernet)
Precondition
The SITOP UPS hardware is connected via the Ethernet interface.
The SITOP-UPS Manager has been installed and configured for Ethernet.
Note
Validity of the information on the SITOP components in this manual
This information only involves the configuration of the settings relevant for the PCU base
software. In addition, all the information and notes in the corresponding manuals of your SITOP
UPS hardware and SITOP UPS Manager apply.
Configuration of the system
4.15 Configuring the SITOP UPS module for use with the PCU Base Software
PCU Base Software (IM10)
Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1 59