EasyManuals Logo
Home>Omron>Controller>E5AR - MANUAL 2

Omron E5AR - MANUAL 2 User Manual

Omron E5AR - MANUAL 2
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #161 background imageLoading...
Page #161 background image
Section 6 Communication (CompoWay/F)
6-22
Communication
(CompoWay/F)
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
Bank change
This command is used to change banks (there are 8 banks numbered
0 to 7). An SP, alarm values, and a PID Set No. are stored in each
bank.
This command can be used in both setting area 0 and setting area 1.
An operation error will result if AT is running in the selected channel.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
Response
"30" "05" "0000"
Response code
SRCMRC
Related
information
Description
Ch Bank No. selected
"00" to "07" 1 0 to 7
"10" to "17" 2 0 to 7
"20" to "27" 3 0 to 7
"30" to "37" 4 0 to 7
"F0" to "F7" All 0 to 7
Command
"30" "05"
SRC
"02"
Instruction
code
Related
information
MRC
Response
"30" "05" "0000"
Response code
SRCMRC

Table of Contents