Section 8 Setting data
8-22
Setting data
8.5 Adjustment 2 level (l.ad2)
Adjustment level 2 contains supplemental settings for adjustment of control such as the time constant of
first order lag operation, move average count, low-cut point of extraction of square root operations, and
settings for proportional control. These functions only appear in the display if they are enabled in Control
initial setting 2 level.
These settings are used to set the time constant of the first order
filter of each input. Data after the first order lag filter elapses is
shown below.
The filter is used to filter out noise elements in the input.
First order lag operation 1: Time constant
First order lag operation 2: Time constant
First order lag operation 3: Time constant
First order lag operation 4: Time constant
lagp.1
lagp.2
lagp.3
lagp.4 First order lag operation function is enabled
Adjustment
level
Operation level
L key less
than 1 second
L key less
than 1 sec
L key less
than 1 second
Adjustment 2
level
L key less
than 1 second
PID setting
level
Approximation
setting
level
L key less
than 1 second
Bank setting
level
L key less
than 1 second
Control in
progress
l. adj
l. ad2
l. bnk
l. pid
l. tec
Power on
lagp.1
map.1
map.2
0.0
0.0
1
1
M
M
M
M
lagp.2
LAGP.1:
First order lag operation 1: Time constant
0.0 - 999.9
LAGP.2:
First order lag operation 2: Time constant
0.0 - 999.9
MAVP.: Move average 1
Move average count
1/2/4/8/16/32
MAVP.: Moveaverage2
Move average count
1/2/4/8/16/32
l.ad2
lagp.3
0.0
0.0
M
lagp.4
LAGP.3:
First order lag operation 3: Time constant
0.0 - 999.9
LAGP.4:
First order lag operation 4: Time constant
0.0 - 999.9
M
map.3
1
M
MAVP.: Moveaverage3
Move average count
1/2/4/8/16/32
Adjustment 2 level
sqrp.1
sqrp.2
ap.1
0.000
0.000
1.000
M
M
SQRP.1 Extraction of square root 1
Low-cut point
0.000 - 9.999
SQRP.2 Extraction of square root 2
Low-cut point
0.000 - 9.999
AP.1
:
Analog parameter
Control rate
-1.999 - 9.999
map.4
1
M
MAVP.: Moveaverage4
Move average count
1/2/4/8/16/32
sqrp.3
sqrp.4
0.000
0.000
M
M
M
SQRP.3: Extraction of square root 3
Low-cut point
0.000 - 9.999
SQRP.4: Extraction of square root 4
Low-cut point
0.000 - 9.999
l.ad2
Function