Section 6 Communication (CompoWay/F)
6-26
Communication
(CompoWay/F)
Move to setting area 1
Use this command to move to setting area 1.
The command is used in setting area 0. Nothing happens if the
command is used in setting area 1.
If the command is used when "Initial setting protect" is set to "2
(Disable move to input initial setting level), an operation error will
result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
Move to protect level
Use this command to move to protect level. Protect level is explained
in "5.5 Protecting settings" (P.5-24).
This command is used in setting area 0. If used in setting area 1, an
operation error will result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
Command
"30" "05"
SRC
"07" "00"
Instruction
code
Related
information
MRC
Response
"30" "05" "0000"
Response code
SRCMRC
Command
"30" "05"
SRC
"08" "00"
Instruction
code
Related
information
MRC
Response
"30" "05" "0000"
Response code
SRCMRC