Section 8 Setting data
8-62
Setting data
• One of the following levels can be selected as the monitor item level
setting: Input initial setting level, Control initial setting level, Control
initial setting 2 level, Alarm setting level, Display adjustment level,
Communication setting level, Advanced function setting level,
Expansion control setting level.
•
The monitor item level is added after the Approximation setting level.
• When OFF is selected, the function is disabled (Monitor item level is
disabled).
• Display scan automatically switches through channels on the display
when multiple channels are used on a multi-point input type.
• Display scan only applies to channels that are enabled using
"Number of enabled channels".
• Display scan can be started automatically after the power is turned
on or by pressing the key.
• To have display scan start automatically after the power is turned on,
set "Start display scan after power on" to ON.
• The display scan period is set with "Display scan period". When the
period is set to "0", display scan is disabled.
Monitor item level setting
monl
l.4
Function
Setting
Setting range Units
Default value
off: Disabled monitor item level
l.0 : Input initial setting level
l.1 : Control initial setting level
l.2 : Control initial setting 2 level
l.3 : Alarm setting level
l.4 : Display adjustment level
l.5 : Communication setting level
l.adf: Advanced function setting level
l.exc: Expansion control setting level
− off
Start display scan after power ON
Display scan period
sc-m
sc-t
Multi-point input type
l.4
Function
CH
Setting
Setting data Setting period Units
Default value
Display scan period
0 to 99
(0: Disable display scan)
Sec 2
Start display scan
after power on
off: Disable
on : Enable
− off