6.9 Commands and responses (Communication/CompoWay/F)
6-25
Communication
(CompoWay/F)
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
■ RAM data store
This writes the setting data of Operation, Adjustment, Adjustment 2,
Bank setting, PID setting, and Approximation setting levels to internal
non-volatile memory. For information on these levels, see "4.1 Setting
levels and key operation" (P.4-2).
This command can be used in both setting area 0 and setting area 1.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
■ Software reset
A software reset causes the same operation as turning the power off
and on.
This command can be used in both setting area 0 and setting area 1.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
(No response)
A response is not returned to this operation command.
Response
"30" "05" "0000"
Response code
SRCMRC
Command
"30" "05"
SRC
"05" "00"
Instruction
code
Related
information
MRC
Response
"30" "05" "0000"
Response code
SRCMRC
Command
"30" "05"
SRC
"06" "00"
Instruction
code
Related
information
MRC
Response