7.9 Commands and responses (Communication/Modbus)
7-27
Communication
(Modbus)
■ Auto / Manual
Use this command to select auto or manual operation.
This command is used in setting area 0. If used in setting area 1, an
operation error will result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
When the control mode is set to cascade control, perform the Auto /
Manual operation command of CH2.
The above indicates a normal end. For information on error responses,
see "7.7 Operation commands (Communication/Modbus)" (P.7-14).
■ Initialize settings
This returns all settings to the initial settings.
This command is used in setting area 1. If used in setting area 0, an
operation error will result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
The above indicates a normal end. For information on error responses,
see "7.7 Operation commands (Communication/Modbus)" (P.7-14).
Related
information
Description
Ch Operation mode
H'00
1
Auto
H'01 Manual
H'10
2
Auto
H'11 Manual
H'20
3
Auto
H'21 Manual
H'30
4
Auto
H'31 Manual
H'F0
All
Auto
H'F1 Manual
Command
H’06 H’00 H’00 H’09
Slave
address
Function
mode
Write start
address
Instruction
code
Related
information
CRC-16
2 2 bytes211
Response
H’06 H’00 H’00 H’09
Slave
address
Function
mode
Write start
address
Instruction
code
Related
information
CRC-16
2 2 bytes211
Command
H’06 H’00 H’00 H’0B H’00
Slave
address
Function
mode
Write start
address
Instruction
code
Related
information
CRC-16
2 2 bytes211
Response
H’06 H’00 H’00 H’0B H’00
Slave
address
Function
mode
Write start
address
Instruction
code
Related
information
CRC-16
2 2 bytes211