Section 8 Setting data
8-12
Setting data
8.4 Adjustment level (l.adj)
This level contains settings for the purpose of adjusting control, such as change bank No., AT (Auto-
tuning), enable/disable write via communication, hysteresis adjustment, input shift settings, and SP ramp
settings.
Adjustment
level
Operation level
L key less
than 1 second
L key less
than 1 sec
L key less
than 1 second
Adjustment 2
level
L key less
than 1 second
PID setting
level
Approximation
setting
level
L key less
than 1 second
Bank setting
level
L key less
than 1 second
Control in
progress
l. adj
l. ad2
l. bnk
l. pid
l. tec
Power on
l.adj
Adjustment level
M
M
M
M
M
M
M
BANK: Bank No. 0 - 7
AT: AT execute / cancel OFF /
0 - 8
CMWT: Write via communication
OFF/ON
SPMD: SP mode
LSP/RSP
C-DB: Dead band
-199.99 - 999.99
OF-R:
Manual reset value
0.0 - 100.0
C-SC: Cooling coefficient
0.01 - 99.99
HYS: Hysteresis
(heating)
0.01 - 99.99
CHYS: Hysteresis
(cooling)
0.01 - 99.99
M
M
M
DB:
Position proportional dead band
0.1 - 10.0
OC-H:
Open / close hysteresis
0.1 - 20.0
SPRH: SP ramp rise value
0 - 99999
(0: Disable SP ramp function)
SPRL: SP ramp fall value
0 - 99999
(0: Disable SP ramp function)
M
M
M
MV-S: MV at stop
-5.0 - 105.0
(standard type)∗1
MV-E: MV at PV error
-5.0 - 105.0
(standard type)∗1
DOGN: Disturbance gain
-1.00 - 1.00
∗1 Position proportional type: Completely open / Hold / Completely closed (-1/0/1)
CP: Control period
(heating)
0.2 - 99.0
M
M
C-CP: Control period
(cooling)
0.2 - 99.0
M
M
M
ORL:
MV change rate limit (heating)
0.0 - 100.0
CORL:
MV change rate limit (cooling)
0.0 - 100.0
ISI.1: Input value 1 for
input correction
-19999 - 99999
M
ISS.2: Input correction 2
-199.99 - 999.99
ISS.1: Input correction 1
-199.99 - 999.99
M
M
ISI.2: Input value 2 for
input correction
-19999 - 99999
M
M
M
M
DOTC: Disturbance
time constant
0.01 - 99.99
DO-B: Disturbance rectification band
0.000 - 9.999
DOJW: Disturbance judgement width
-99.99 - 99.99
bank
0
CH
at
off
CH
cmwt
off
spmd
lsp
CH
c-sc
1.00
CH
c-db
0.00
CH
of-r
50.0
CH
hys
0.10
CH
M
chys
0.10
CH
cp
20.0
CH
c-cp
20.0
CH
db
2.0
CH
oc-h
0.8
CH
sprh
CH
sprl
CH
mV-s
0.0
CH
mV-e
CH
0.0
orl
CH
corl
0.0
CH
isi.1
-200.0
CH
iss.1
0.00
CH
isi.2
1300.0
CH
iss.2
0.00
CH
dogn
0.6 5
CH
dotc
1.00
CH
do-b
CH
0.000
dojw
0.00
CH
SPRU:SP ramp time unit
EU /s ec: S, EU / min: M,
EU / hour: H
spru
m
CH
M
0.0
0.0
0.0
M