Section 8 Setting data
8-30
Setting data
8.7 PID setting level (l.pid)
This level contains the PID value, MV limit, and alarm settings for each PID set. To move to a PID set, use
the "Display PID set select" setting at the beginning of PID setting level.
Use this setting to select the PID set that you wish to display.
• Set the number of the PID set that you wish to display.
• Up to 8 PID sets (PID Set Nos. 1 to 8) can be used. PID values, MV
upper and lower limits, and automatic selection range upper limit are
stored in each PID set.
* Selected PID set
● Related setting data
"Bank No." (Adjustment level) (P.8-13)
Display PID selection
d.pid
Adjustment
level
Operation level
L key less
than 1 second
L key less
than 1 sec
L key less
than 1 second
Adjustment 2
level
L key less
than 1 second
PID setting
level
Approximation
setting
level
L key less
than 1 second
Bank setting
level
L key less
than 1 second
Control in
progress
l. adj
l. ad2
l. bnk
l. pid
l. tec
Power on
l.pid
PID setting level
d.pid
Display PID selection
1
PID1
PID2
PID3
2
3
8
PID8
D
U
M
M
M
M
M
M
M
M
M
M
1.p
10.00
1.i
233.0
1.d
40.0
1.ol-h
100.0
1.ol-l
0.0
M
1.
1450.0
8.p
10.00
8.i
233.0
8.d
40.0
8.ol-h
100.0
8.ol-l
0.0
M
M
M
8.
8.P: PID8 Proportional band
0.00 - 999.99 (standard)∗1
8.I: PID8 Integral time
0.0 - 3999.99 (standard,
position proportional
(closed control))∗2
8.D:PID8 Derivative time
0.0 - 3999.9
8.OL-H:PID8 MV upper limit
MV lower limit
0.1 - 105.0
8.OL-L:PID8
MV lower limit
-5.0 - MV upper limit - 0.1
8.AUT:PID8
Automatic selection range
upper limit
-10% to 110% (temperature)
of sensor setting range∗3
1450.0
∗1 Position proportional type: 0.01 - 999.99
∗2 Position proportional (floating control) type: 0.1 - 3999.9
∗3 Analog type: -10% to 110% of scaling display range, with
a maximum of -19999 to 99999
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
aut
aut
CH
l.pid
Function
Setting
Setting data Setting range Units
Default value
Display PID
selection
1 to 8 − *
Reference