6.9 Commands and responses (Communication/CompoWay/F)
6-23
Communication
(CompoWay/F)
■ AT execute
This command runs AT. On the E5AR/ER, the PID Set No. must be
specified when running AT.
To specify the currently selected PID Set No. (the PID set currently
used for operation), set the lower byte of the related information to "0".
This command is used in setting area 0. If used in setting area 1, an
operation error will result. An operation error will also result in the
following situations:
• "Run/Stop" of the specified channel is set to "Stop".
• "Auto / Manual" of the specified channel is set to "Manual".
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
■ AT cancel
Related
information
Description
Ch Command
"00" to "08" 1
00: Currently selected PID Set No.
01 to 08: Specifies PID Set No. 1 to 8
"10" to "18" 2
10: Currently selected PID Set No.
11 to 18: Specifies PID Set No. 1 to 8
"20" to "28" 3
20: Currently selected PID Set No.
21 to 28: Specifies PID Set No. 1 to 8
"30" to "38" 4
30: Currently selected PID Set No.
31 to 38: Specifies PID Set No. 1 to 8
"F0" to "F8" All
F0: Currently selected PID Set No.
F1 to F8: Specifies PID Set No. 1 to 8
Command
"30" "05"
SRC
"03"
Instruction
code
Related
information
MRC
Response
"30" "05" "0000"
Response code
SRCMRC
Related
information
Description
Ch Operation
"00" 1 Stops AT
"10" 2 Stops AT
"20" 3 Stops AT
"30" 4 Stops AT
"F0" All Stops AT
Command
"30" "05"
SRC
"0A"
Instruction
code
Related
information
MRC