3.11.3.3 STO function with safety switching device for applications with
fieldbusses
In this chapter you can read about:
Energize and deenergize circuitry ..................................................................................... 95
Function description for fieldbus applications:
................................................................... 96
Energize and deenergize circuitry
GND24V
Quit
A2
A1
S3
EN
S1 I4 I3 I2 I1 X1 X2
S2 Q1 Q2 Q3 Q4
+24V
S2
S1
motor
motor
Safety door open
Schutztür offen
Danger Zone
Gefahrenbereich
Fieldbus
Fieldbus
UE410-MU3T5
Delay
Time
X14.4
X14.3
X14.2
X14.1
Energize
Compax3M
X3
X14.4
X14.3
X14.2
X14.1
Energize
Compax3M
X3
S
4
S
5
&
* *
&
+24V
*
Not-Aus
Emergency
switch off
*
* With Profibus:
Status change in:
0 -> 1 SB1
SC1
1 -> 0 SA2
* with CANopen, Devicenet, Ethernet Powerlink and Ethercat:
Status change in:
0 -> 1 Operation enable
1 -> 0 Switched On Disabled
The operating instructions of the UE410-MU3T5 safety control must be observed.
The Compax3M devices and the UE410-MU3T5 safety control must be mounted in
the same control cabinet.