EasyManuals Logo
Home>KEB>Control Unit>COMBIVERT F5-H

KEB COMBIVERT F5-H User Manual

KEB COMBIVERT F5-H
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
Operating and appliance data
© KEB, 2012-10 COMBIVERT F5-A, -E, -H Page 7.1 - 21
7
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
Sy.07 Power unit code 0007h RW - + 0 6 1 - 5
Following values for the baud rate of the serial interface are possible:
Parameter value Baud rate
0 1200 Baud
1 2400 Baud
2 4800 Baud
3 9600 Baud
4 19200 Baud
5 (default) 38400 Baud
6 55500 Baud
If the value for the baud rate is changed via the serial interface, it can be changed again only by the keyboard
or after adapting the baud rate of the master, as no communication is possible with different baud rates of
master and slave.
Should problems occur at the data transmission choose a transfer rate of maximal 38400 baud.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
SY.08 Bus synchron time 0008h RW - + 0: off 65000 1 µs 0
The time, within which the control synchronized onto an external clock pulse (sercos), is entered in this para-
meter. If no sychnronization takes place, an error or status message (E.SbuS or A.SbuS) , depending on the
adjusted behaviour, is output. The value „off“ deactivates the function.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
Sy.09 HSP5 watchdog time 0009h RW - + 0: off 10.00 0.01 s 0
The HSP5 watchdog function monitors the communication of the HSP5 interface (control card - operator; or
control card - PC). After expiration of an adjustable time (0,01...10 s) without incoming telegrams, the response
adjusted in Pn.5 is triggered. The value „off“ deactivates the function.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5-H and is the answer not in the manual?

KEB COMBIVERT F5-H Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5-H
CategoryControl Unit
LanguageEnglish

Related product manuals