11 What to Do!
11 - 12
Vision System FH/FHV/FZ5 Series Users Manual (Z365)
Trigger signal (input signal) not accepted
Are the cables connected correctly?
Is the signal cable disconnected?
You can check the communication status in the Confirmation window.
Refer to Parallel Communications - Testing Communications in the Vision System FH/FHV/FZ5
Series User's Manual for Communications Settings (Cat. No. Z342)
Are windows other than the Main screen (the Edit Flow window, etc.) displayed?
Are there any setting windows open?
* A setting window is defined as a window that opens separately such as the Edit Flow window
and the Scene Maintenance window.
Signals cannot be output to external devices
Is the trigger signal input?
Are the cables connected correctly?
Is the signal cable disconnected?
You can check the communication status in the Confirmation window.
Refer to Parallel Communications - Testing Communications in the Vision System FH/FHV/FZ5
Series User's Manual for Communications Settings (Cat. No. Z342).
Is test measurement being performed?
Data cannot be output to external devices during test measurement.
GATE signals are not output
Wiring:
Are parallel cables wired correctly?
Please check if GATE signals are being recognized by the receiving side (such as the PLC) by
turning the GATE signal ON/OFF in the System - Communication - Parallel - Confirmation win-
dow.
Output setting:
Is parallel judgement output or parallel data output set for the scene? Is an expression input for
parallel data output?
GATE signals are not output unless these items are specified.
Is [Output] set to ON in the layout setup?
Set whether to produce external outputs for each layout.
Timing:
Are the parallel communication settings (output cycle and output time) set to a length sufficient for
the PLC to recognize?
Could the System - Communication - Parallel output control be set to handshaking or synchroni-
zation output?
These settings influence the GATE output timing.
Refer to Parallel Communications - Time Charts in the Vision System FH/FHV/FZ5 Series User's
Manual for Communications Settings (Cat. No. Z342).
11-2-4 About Parallel Interface

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron fh-1 series and is the answer not in the manual?

Omron fh-1 series Specifications

General IconGeneral
BrandOmron
Modelfh-1 series
CategoryMachine Vision Systems
LanguageEnglish

Related product manuals