140 Enable/Disable Staged Startup
10.24.2 Enable/Disable Staged Startup
Users can enable or disable the Staged Startup feature on the Staging screen. The Staged
Startup process is used to control how the temperature increases (heats) in the system.
To enable or disable Staged Startup, do the steps that follow:
1. From the Home screen, touch the Staging button.
2. On the Staging screen, do one of the tasks that follow:
• To enable Staged Startup, touch the Enable check box that is below Staged Startup,
and then touch the Accept button in the Warning window that shows on the screen.
A check mark shows in the Enable check box.
• To disable Staged Startup, touch Enable check box that is below Staged Startup to
clear the check mark.
Table 10-12 Staging Screen Settings
Item Description
Staged Startup Enable Enables or disables the staged startup sequence.
Run Last Stage Indefinitely When enabled, all zones in the last assigned stage will not change
to their normal setpoint when all zones have achieved the stage
setpoint and the soak timer has completed.
Stage x Soak Timer The time duration at each stage the zones “soak” at their stage
setpoints before the next stage begins.
Stage x Temperature The temperature setpoint that the zone heats to during stage x.
Stage x Power The setpoint that is used when zones are in manual regulation
during stage x.
Staged Shutdown Enable Enables or disables the staged shutdown sequence.
Staged Shutdown Override
Limit
This limit is used during staged shutdown. If all the zones in the
stage have not decreased to the stage setpoint temperature in the
override time limit, the system automatically starts the next stage.
If no zones are assigned to the next stage, then the system will
turn off.