BATTERY TIMER STATUS
Description: Displays the last 50 recorded discharges in a tabular format. The
information displayed includes the duration of the battery discharge, the time and date at
which the discharge began, the lowest recorded plant voltage during the discharge, and
the average plant load.
Command Level: 6
Syntax: BATTERY TIMER STATUS
BA TI ST
Comments: none
Notes: There may be less than 50 entries if the system is new or the history has been
cleared with the BATTERY TIMER CLR command. The discharges are recorded as D01
through D50. D01 is the most recent discharge and D50 is the oldest. The oldest
discharge is removed from record when more than 50 discharges are completed.
Related Commands: BATTERY TIMER CLR, BATTERY TIMER CSV, BATTERY
TIMER SET
Example:
Command<6>: BATTERY TIMER STATUS
BATTERY DISCHARGE HISTORY
-Dur- ---AC FAIL---- --VDC- -AMPS- -Dur- ---AC FAIL---- --VDC- -AMPS-
D01 00:00 09:20 02/26/03 27.00 88.00 D26 00:07 09:12 02/24/03 27.00 88.00
D02 00:07 09:12 02/26/03 27.00 88.00
…
D25 00:07 09:12 02/25/03 27.00 88.00
WARNING!!! THE SYSTEM IS ON BATTERY
D00 00:00 09:20 02/26/03 27.00 88.00
___________________________________________________________________________________
Command<6>: BATTERY TIMER STATUS
BATTERY DISCHARGE HISTORY
-Dur- ---AC FAIL---- --VDC- -AMPS- -Dur- ---AC FAIL---- --VDC- -AMPS-
D01 00:00 09:20 02/26/03 27.00 88.00 D26 00:07 09:12 02/24/03 27.00 88.00
D02 00:07 09:12 02/26/03 27.00 88.00
…
D25 00:07 09:12 02/25/03 27.00 88.00
The system is NOT on battery