Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-144 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
REPORT
Description: Displays report information.
Command Level: 6
Syntax: REPORT
Comments: Displays parameters related to the alarm reporting function.
Refer to the command SET REPORT for additional information concerning the operation
of the system alarm reporting function.
Notes: Parameters displayed include:
System Alarm Report mode, which enables the reporting and allows the user to
choose between single (system alarm reporting is considered successful if the
system connects with a modem or sends an Email) or continuous (system alarm
reporting is considered successful when the user issues an ACK command).
User Calling Sequence, which allows the programming of users in the order in which
the system will call or Email in an attempt to communicate an alarm indication.
Retry Time, which is the time interval between the calling or Emailing of the last
person designated in the user calling sequence and the recalling or Emailing of the
first user in the sequence.
Auto-logoff Time, which is the interval the system waits with a pending report before
issuing a priority message, and logging the user off.
Related Commands: SET REPORT
Example:
Command<6>: REPORT
System Alarm Report mode: Single
User Calling Sequence: 6 5 4
Retry Time: 10m
Auto-logoff Time: 60sec