Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-170 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET LIMITS
Description: Permits setting of the four analog limits for each input.
Command Level: 5
Syntax: SET LIMITS [channel_type_node_number_channel_number]
SE LI [channel_type_node_number_channel_number]
Comments: To utilize the special rate computations by the system, analog channel
alarm limits names should include the text SIZ or CAP.
Notes: Any user setting limits using this command will have his name and this action
recorded in the event log. Changing the limits could affect the analog alarm log
conditions; which could affect alarm log entries; which could initiate a phone report or
Email message.
If a limit is changed when an alarm is active which deactivates the alarm condition, the
alarm remains active in the alarm log and will not be shown as cleared. Also, no retired
alarm notification will be sent.
Except for the LPS Distribution Channels, limits cannot be set for analog LPS channels.
These are set and controlled by the MCA.
Limits can also be programmed when a channel is configured. If the only change
required to an existing channel is to change the limits, the SET LIMITS command
eliminates the need to proceed through an entire channel configuration sequence.
Related Commands: LIMITS
Example:
Command<5>: SET LIMITS A0001
ANALOG CHANNEL 1 ALARM LIMITS AS OF 20:35:17 ON 02/09/01.
Chan Description
A0001 Analog Channel 1
Limit / Name Class Condtype Ntfc Svef
70.0 H HVA2 TOOHIGH CR SA
Condition Description
VOLTAGE IS TOO HIGH
60.0 H HVA1 HIGH MJ NSA
Condition Description
VOLTAGE IS HIGH
50.0 L LVA1 LOW MN SA
Condition Description
VOLTAGE IS LOW
40.0 L LVA2 TOOLOW CR NSA
Condition Description
VOLTAGE IS TOO LOW
Limit 1 Enabled: Yes
Limit 1 Enabled (Y or N):
Limit 1 Value: 70.0
Limit 1 Value:
Limit 1 Type: H
Limit 1 Type is High or Low (H or L):
Limit 1 Name: HVA2