Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-364 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET-THRESHOLD
(SET-TH-{EQPT})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-417
General Description: Instructs LMS1000 to set threshold levels (alarm limits) for a
monitored parameter that, when exceeded, will trigger an automatic message.
These threshold levels may apply to one or more equipment units, facilities, etc. within
LMS1000.
An entry is made in the LMS1000’s event log indicating this command was executed by
the current sessions user.
Related Commands: RETRIEVE-THRESHOLD
Related Messages: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: SET LIMITS <tn>
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter identifies the equipment for which threshold
levels are being set. Specifying a value of ALL requests setting of thresholds for all
access identifiers of the type defined by the command code modifier. A NULL value is
not permitted for this parameter. Invalid values received for this parameter return an
error response with the error code IIAC.
<montype>
The monitor type (<montype>) parameter identifies the particular monitored parameter for
which the threshold is being set. Values are derived from the MONITOR TYPE attribute
of the LMS1000 analog or function channel configuration. This parameter must contain a
suffix to designate the type of threshold to be set. The suffix is separated from the
monitor type parameter by a hyphen and takes the form LT or HT to indicate low or high
threshold types, respectively.
Example: DCVOLT-LT
Parameter grouping cannot be used with this parameter. This parameter cannot have a
value of NULL. Valid values for this parameter can contain only alpha characters. This
parameter is required in the input. Invalid values received return an error response with
the error code IDNV.
<thlev>

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson LMS1000 and is the answer not in the manual?

Emerson LMS1000 Specifications

General IconGeneral
BrandEmerson
ModelLMS1000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals