SET ACO
Description: Releases any relays that are energized due to analog or binary alarms,
provided the relays are configured for ACO operation.
Command Level: 4
Syntax: SET ACO
SE AC
Comments: none
Notes: Any user setting the alarm cutoff will have his name and this action recorded in
the event log. If an analog or binary alarm were to clear and then turn in again, it would
then affect relay control programs. Relays configured as alarm types that are affected by
a SET ACO will affect the alarm log information. When the output turns off, the
associated log entry will have its cleared time stamped with the current time. Because
this alarm could affect the alarm log, this command could initiate some phone reports or
Email messages. Only relays configured for ACO will be affected by this command.
Related Commands: ACO
Example:
Command<4>: SET ACO
The following alarms are cutoff:
Chan Description Value Units Alarm Limit and Class
A0001 Analog Channel 1 +20.1 Amps 20.0 H - Hi Limit 2 MAJOR
Chan Description Status Alarm Status / Class
B0001 Binary Channel 1 CO active MINOR