User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-163
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET DEFAULTS
Description: Returns the user programmable parameters shown in Table 3-2 back to
their default (factory) settings.
Parameter Default Setting
Unit Name Central Office
Unit Number 1
Unit TCP/IP Address 0.0.0.0
GET Community String public
SET Community String private
Trap Addresses (none set)
SNMP Version (for traps sent) V2
Number of Rings before Answering 1
User Timeout Period 300 seconds
Logon Password Number of Access Level Required (1-6)
System Alarm Report Mode Off
User Calling Sequence (none defined)
Retry Time (System Alarm Report) 10 minutes
Auto-Logoff Time 60 seconds
Sequencer Standby Start Delay 15 seconds
Sequencer Failsafe Timer 60 seconds
AC Restoration Qualification Timer 0 (disabled)
Rectifier Sequencing Routines Y
Table 3-2
Default Settings for System Parameters
Command Level: 6
Syntax: SET DEFAULTS
SE DE
Comments: The user will have to type the complete word "YES" when prompted to set
the defaults.
Notes: This command will permanently destroy any information the user has
programmed, including alarm log information and user configuration. This command will
not destroy the event log, or change any communications parameters.
Related Commands: none
Example:
Command<6>: SET DEFAULTS
Execution of this command will DESTROY ALL SYSTEM CONFIGURATIONS
and could result in ALARM CONDITIONS !!
Do you wish to set defaults(YES or No)? N
Defaults NOT set