Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-206 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET LPS SYSTEM TEMPSLOPE
Description: Sets the "battery charge temperature compensation feature's
compensation slope" value.
Command Level: 6
Syntax: SET LPS SYSTEM TEMPSLOPE
SE LP SY TEMPS
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set lps sys temps
Temperature Compensation Slope: 0.111 V/DegC
Temperature Compensation Slope: 0.200
Temperature Compensation Slope NOT CHANGED!
NOTE, THE "0." IS ENTERED FOR THE USE
NOTE, NEED PROBE INSTALLED
___________________________________________________________________________________
Command<6>: set lps sys temps
Temperature Compensation Slope: 0.111 V/DegC
Temperature Compensation Slope: 0.15
New Temperature Compensation Slope Accepted.
___________________________________________________________________________________
Command<6>: set lps sys temp
Temperature Compensation Slope: 0.100 V/DegC
Temperature Compensation Slope: 0.0
Temperature compensation DEACTIVATED!
___________________________________________________________________________________
Command<6>: set lps sys temps
Temperature Compensation Slope: 0.150 V/DegC
Temperature Compensation Slope: 0..1
Temperature compensation DEACTIVATED!
NOTE, ANYTHING THAT EVALUATES TO ZERO DEACTIVATE TC
___________________________________________________________________________________
Command<6>: set lps sys temp
Temperature Compensation Slope: 0.000 V/DegC
Temperature Compensation Slope: 0.1
New Temperature Compensation Slope Accepted.