User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-327
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
INITIALIZE-LOG(INIT-LOG)
Referenced In: TA-NWT-000200, Issue 5; pg. 132
General Description: Instructs LMS1000 to initialize (i.e., clear) the specified log (alarm
or event).
When this command is executed, it clears the contents of the existing log.
An entry is made in the LMS1000’s event log indicating this command was executed by
the current sessions user. The event description indicates that the specified log was
cleared.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: CLR LOG, CLR EVENTS
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter does not apply. The only valid value for this
parameter is NULL. Invalid values received for this parameter return an error response
with the error code IIAC.
<lognm>
This is the name of the log. Valid values for this parameter are the text strings ALARM
and ACTIV. The string ALARM specifies clearing the LMS1000’s alarm log, and the
string ACTIV specifies clearing the LMS1000’s event log. Invalid values received for this
parameter return an error response with the error code IDNV.
<stadat>
This parameter is not implemented in LMS1000, and must be the value NULL. Null
specifies a default value of the current date. Invalid values received for this parameter
return an error response with the error code INUP.
<statm>
This parameter is not implemented in LMS1000, and must be the value NULL. Null
specifies a default value of the current time. Invalid values received for this parameter
return an error response with the error code INUP.
LMS1000 Response Format Variations: None