Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-204 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET LPS SYSTEM TEMPCOMPMAX
Description: Sets the "battery charge temperature compensation feature's maximum
voltage" value.
Command Level: 6
Syntax: SET LPS SYSTEM TEMPCOMPMAX
SE LP SY TEMPCOMPMA
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set lps sys tempcompmax
Maximum Temp. Compensation Voltage: 56.50 VDC
Maximum Temp. Compensation Voltage: 56.7
Maximum Temp. Compensation Voltage NOT CHANGED!
___________________________________________________________________________________
Command<6>: set lps sys tempcompmax
Maximum Temp. Compensation Voltage: 56.50 VDC
Maximum Temp. Compensation Voltage: 55.9
New Maximum Temp. Compensation Voltage Accepted.