User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-143
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
RATE
Description: Compares the maximum peak value and the highest hourly average to an
alarm limit, and presents the results as percentage values.
Command Level: 1
Syntax: RATE
R
Comments: These percentages indicate the closeness of the highest hourly average
and maximum peak values to the designated alarm value, and indirectly, the percentage
of the measured value to capacity. To use this feature, one of two character phrases
must appear in the analog channel's alarm limit name. These two phrases are "CAP" (for
capacity) and "SIZ" (for size). Also, the "Unit Text" for this analog channel must be
"AMPS". Any time the RATE command is entered, and either of these two phrases
appear in an analog channel's alarm limit name and the analog channel's Unit Text is set
for AMPS, the system computes the two percentages and displays the resulting
information.
Notes: none
Related Commands: none
Example:
Command<1>: rate
RATING PERCENTAGES AS OF 15:34:38 ON 04/29/01.
Chan Description Limit/Name Max Hrly Avg. Max min Avg.
A0001 PBD02 LOAD 11 300.0 FUSE SIZE 118.9, 40% 119.1, 41%
A0001 PBD02 LOAD 11 200.0 FUSE CAP. 118.9, 59% 119.1, 60%
A0002 PBD02 LOAD 12 300.0 FUSE SIZE 87.4 , 58% 87.5 , 58%
A0002 PBD02 LOAD 12 200.0 FUSE CAP. 87.4 , 87% 87.5 , 87%
A0003 PBD02 LOAD 13 300.0 FUSE SIZE 44.0 , 29% 44.2 , 29%
A0003 PBD02 LOAD 13 200.0 FUSE CAP. 44.0 , 44% 44.2 , 44%