User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-151
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SEQUENCE
Description: Lists the sequencer option configuration parameters, and displays
sequencer status.
Command Level: 1
Syntax: SEQUENCE
SEQ
Comments: Information displayed includes the status of the standby sequencer, the
Standby On/Proper Operate binary input number, and the Standby Start Delay. The AC
Sequencer status is also listed, along with the AC Fail/Transfer binary input number, the
Input Type, the Sequencer Failsafe Time, and AC Restoration Qualification Time.
Notes: none
Related Commands: SET SEQUENCE
Example:
Command<1>: SEQUENCE
RECTIFIER SEQUENCING ROUTINES Current Setting (DISABLED or ACTIVE)
SEQUENCER OPTIONS:
AC Sequencer: Off
AC Fail/Transfer Input = B0001
Input type: AC Fail
Standby Sequencer: Off
Standby On/Proper Operate Input = B0001
Standby Start Delay: 15sec
Sequencer Failsafe time: 100sec
AC Restoration Qualification time: 100sec