User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-359
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET-ATTRIBUTE
(SET-ATTR-{EQPT})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-385
General Description: Instructs LMS1000 to set the current notification code associated
with the specified events.
An entry is made in the LMS1000’s event log indicating this command was executed by
the current user.
Related Commands: RETRIEVE-ATTRIBUTE
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations: The command code modifier COM is not
supported.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests setting of
attributes for all access identifiers of the type defined by the command code modifier. A
NULL value is not permitted for this parameter. Invalid values received for this parameter
return an error response with the error code IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the alarm conditions being set.
This parameter is an attribute of the LMS1000 channel or limit configuration.
Valid values for this parameter are as follows:
CR critical alarm
MJ major alarm
MN minor alarm
NA not alarmed
NR not reported
NULL defaults to NA
Invalid values for this parameter return an error response with the error code IDNV.
<condtype>
The condition type (<condtype>) parameter identifies the type of event for which a
notification code (<ntfcncde>) parameter is being changed. This parameter is an
attribute of the LMS1000 channel or limit configuration. This parameter is required in the
input. Invalid values for this parameter return an error response with the error code
IDNV.