Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-324 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
ENTER-USER-SECURITY
(ENT-USER-SECU)
Referenced In: TR-NWT-000835, Issue 3; pg. 3-71
General Description: Activates a user and enters the specified security parameters for
this user. These security parameters consist of the user identifier (<uid>) parameter (i.e.,
LMS1000 user name), privilege identifier (<pid>) parameter (i.e., LMS1000 user
password), calling identifier (<cid>) parameter (i.e., LMS1000 user primary phone
number), and user access privilege (<uap>) parameter (i.e., LMS1000 user access level).
When executed, the command sets the USER ACTIVE attribute of this user’s LMS1000
user configuration to Y. The command also sets the USER NAME, PASSWORD,
PRIMARY PHONE, and ACCESS LEVEL attributes of this user’s LMS1000 user
configuration to the specified values. The following attributes of this user’s LMS1000
user configuration are also set as indicated.
Callback N
Alternate Phone (none entered)
Report Device X25
Report Mode TL1
If the specified access identifier (<aid>) parameter matches the NAME attribute of an
inactive LMS1000 user, the following attributes for this LMS1000 user remain unchanged.
If the specified access identifier does not match the NAME attribute of an inactive
LMS1000 user, the following attributes of this user’s LMS1000 user configuration are set
to the default values indicated below.
From Day 1
Thru Day 7
From Hour 0
Thru Hour 23
TL1 Report Condition Interval 0
Report Retry Time 15
An entry is made in the LMS1000’s event log indicating this command was executed by
the current sessions user. The event description indicates that the specified user was
activated.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter is the same value as the user identifier (<uid>)
parameter for the user who is being activated. The user identifier parameter is the new