User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-273
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
STATS
Description: This command lists the statistics for Analog and Function channels.
Command Level: 1
Syntax: STATS[node_designator] [channel_range] [node_range] [group_designator]
STATS A
STATS F
STATS A[[node_number]channel_number]
STATS F[channel_number]
ST[node_designator] [channel_range] [node_range] [group_designator]
Comments: Information presented includes the three hourly averages and their time
and date of occurrence, the time and date of the peak value, and the time and date of the
minimum value recorded. Entering the command STATS without a number n will display
the statistics for all analog inputs and function channels.
Notes: Any statistic showing a zeroed date and time means the statistic has been
recently reset. When using channel_range, only channel types A or F are valid.
When readings have not yet been taken, the Stats will display the smallest possible
reading for high or maximum averages and the highest possible reading for the minimum.
Related Commands: CLR STATS
Example:
Command<1>: STATS
A0001 stats: Analog Channel 1. Last reset 03/22/01 02:12:18
#1 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
#2 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
#3 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
Maximum of -20000 Amps at 00/00/00 00/00.
Minimum of 20000 Amps at 00/00/00 00/00.
A0002 stats: Analog Channel 2. Last reset 03/21/01 23:56:38
#1 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
#2 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
#3 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
Maximum of -0.000 Amps at 03/22/00 00:08.
Minimum of -0.000 Amps at 03/21/00 23:56.
A0003 stats: Analog Channel 3. Last reset 03/21/01 23:56:38
#1 High Hrly Avg of 1.970 Amps at 03/22/00 01:00.
#2 High Hrly Avg of 0.001 Amps at 03/22/00 00:00.
#3 High Hrly Avg of -20000 Amps at 00/00/00 00/00.
Maximum of 5.163 Amps at 03/22/00 01:59.
Minimum of 0.001 Amps at 03/22/00 00:59.
___________________________________________________________________________________
Command<6>: stats f
F0001 stats: Function Channel 1. Last reset 03/21/01 23:56:38
#1 High Hrly Avg of -99999 Amps at 00/00/00 00/00.
#2 High Hrly Avg of -99999 Amps at 00/00/00 00/00.
#3 High Hrly Avg of -99999 Amps at 00/00/00 00/00.
Maximum of 0.000 Amps at 03/22/00 00:09.
Minimum of 0.000 Amps at 03/22/00 00:09.