SET LPS
Description: Lists all LPS MCA Interface commands that begin with the command SET,
and then prompts the user to enter one of the displayed options.
Command Level: NA
Syntax: SET LPS [command]
SE LP [command]
Comments: none
Notes: Only commands available to the current user are listed. The list in the example
is for a user that has access to level 6 commands.
Related Commands: SET, SET VORTEX
Example:
Command<6>: set lps
Set What:
SYSTEM PCU MESSAGE PASSWORD CANIO
? sys
What system parameter:
FLTVOLT TSTEQVOLT HVS CURLIMIT HIVLTALM1
HIVLTALM2 BATONDISCH VERYLOWVOLT LOADCURRENT LOADACURRENT
LOADBCURRENT TSTEQMODE NAGTIMER TSTEQTIME TEMPSLOPE
TEMPCOMPMAX TEMPCOMPMIN HI1TEMPALM HI2TEMPALM LOW1TEMPALM
LOW2TEMPALM RLYTSTTIME RLYONTEST RLYOFFTEST USECELSIUS
USEFAHRENHEIT EQMULTIPLIER UPDATEINV
? flt
Float Voltage: 52.08 VDC
Float Voltage: 52.1
New Float Voltage Accepted.
___________________________________________________________________________________
Command<6>: set lps
Set What:
SYSTEM PCU MESSAGE PASSWORD CANIO
? pcu
Which PCU (bay#-pcu#)? 01-01
Turn PCU 01-01 ON or OFF? off
PCU 01-01 set OFF