Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-374 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
REPORT CONDITION
(REPT COND {EQPT/COM})
Referenced In: TR-NWT-000833, Issue 5; pg. 5-21
General Description: Provides a periodic report of selected LMS1000 standing
conditions such as equipment units out of service, etc. The reporting period and
conditions are defined in the LMS1000's requirements.
Related Commands: RETRIEVE-CONDITION
Related Messages: REPORT EVENT
LMS1000 Equivalent: None
LMS1000 Message Format Variations:
<aid>
Identifies the single entity in the LMS1000 to which the condition pertains. If the
message code modifier is COM, then this parameter must be COM, indicating a system-
wide condition that is not specific to a particular sub-unit. A NULL value is not permitted
with this parameter. Parameter grouping cannot be used with this parameter.
<ntfcncde>
This is the notification code parameter associated with a single alarm condition given in
this block.
Valid values are as follows:
CR Critical alarm
MJ Major alarm
MN Minor alarm
NA Not alarmed
NR Not reported when the event occurs
A NULL value for the notification code defaults to NA.
Values are derived from the NOTIFICATION CODE attribute of the LMS1000 channel or
limit configuration with which the alarm condition is associated. Parameter grouping
cannot be used with this parameter.
<condtype>
This is the condition type parameter of the alarm indication given in this block. Values
are derived from the CONDITION TYPE attribute of the LMS1000 channel or limit
configuration with which the alarm condition is associated. Parameter grouping cannot
be used with this parameter.
<srveff>
This is the service effect parameter associated with a single alarm condition given in this
block.