User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-209
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET LPS SYSTEM TSTEQVOLT
Description: Sets the LPS "test/equalize output voltage" value.
Command Level: 6
Syntax: SET LPS SYSTEM TSTEQVOLT
SE LP SY TST
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service
interruption. Refer to the LPS instruction manual's test/equalize adjustment procedure
for details.
The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set lps sys tst
Test/Equalize Voltage: 52.00 VDC
Test/Equalize Voltage: 52.1
New Test/Equalize Voltage Accepted.