User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 2. Operating LMS1000 Page 2-19
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
ACKNOWLEDGING SYSTEM ALARMS
If the System Alarm Report Mode parameter (SET REPORT command) is set to
CONTINUOUS, the system continues to call or Email the User at the programmed retry
interval until the user acknowledges the alarm. Acknowledgement of an alarm is done by
logging on with a terminal and entering the command ACK.
Using the ACKnowledge Command: If a user issues an ACKnowledge command, the
user’s ID number is tagged to all alarm log entries not previously acknowledged. If the
ACK command is issued after a user receives a pending system alarm report message,
the auto-logoff and system alarm report will be aborted.
GETTING ANALOG AND FUNCTION CHANNEL STATISTICS
The statistics available for any analog or function channel include the three highest clock
hourly averages and their time and date of occurrence, the time and date of the peak one
minute average value, and the time and date of the minimum one minute average value.
The time of the last reset is also shown. These statistics are retained in battery-backed
memory.
Commands STATS and CLR STATS: Statistics can be obtained through the command
STATS. The current statistics can be cleared to allow other statistic values to be
recorded using the command CLR STATS. The statistics for each analog and function
channel can be cleared independently by using the modifier An or Fn (n=channel
number) after typing the characters CLR STATS (ex. CLR STAT A0001 or CLR STAT
F0001). The command STATS is available to a user programmed for access to level 1
commands. The command CLR STATS is available to users programmed for access to
level 4 commands.
USING THE SCAN FEATURE
The user can set the time interval between scan data output lines when scanning an
individual channel. The interval can be specified from 1 to 600 seconds. This is done by
entering a modifier (1 through 600) at the end of a scan command line. If no modifier is
entered, a single line of scan data is displayed. (ex. SCAN A0012 20, would output one
line of scan data for analog channel A0012 every 20 seconds.)