Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-176 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET LPS CANIO
Description: Set LPS MCA CAN I/O circuit card parameters.
Command Level: 6
Syntax: SET LPS CANIO [bb-dd], bb = LPS Bay #, dd = LPS Bay Slot #
SE LP CA [bb-dd], bb = LPS Bay #, dd = LPS Bay Slot #
Comments: Prompted to select which LPS MCA CAN I/O circuit card, then which
parameter to set (designate the alarm state for MCA CAN I/O circuit card binary inputs,
designate MCA CAN I/O circuit card analog inputs as "auxiliary" or "distribution", or set
the scale factor for MCA CAN I/O circuit card analog inputs and outputs).
Notes: None
Related Commands: none
Example:
Command<6>: set lps canio 01-04
What CAN I/O board parameter:
LOADTYPE SCALE BINARY
?
___________________________________________________________________________________
Command<6>: set lps canio
Which CAN I/O board (bay#-board#)? 01-04
What CAN I/O board parameter:
LOADTYPE SCALE BINARY
? loadtype
CAN I/O board 01-04 set as DIST type
Set load type to AUX or DIST? aux
CAN I/O board 01-04 set as AUX type
___________________________________________________________________________________
Command<6>: set lps canio
Which CAN I/O board (bay#-board#)? 01-04
What CAN I/O board parameter:
LOADTYPE SCALE BINARY
? scale
Set scale for INPUT or OUTPUT? output
Enter full scale Amps (100 - 20000): 100
CAN I/O board 01-04 Output scale set
___________________________________________________________________________________
Command<6>: set lps canio
Which CAN I/O board (bay#-board#)? 01-04
What CAN I/O board parameter: