Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-342 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
RETRIEVE-ATTRIBUTE
(RTRV-ATTR-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-223
General Description: Instructs LMS1000 to send the current notification code
associated with the specified events.
Related Commands: SET-ATTRIBUTE
LMS1000 Access Level: 2
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations: The command code modifier COM is not
supported.
The <aid>, <ntfcncde>, and <condtype> parameters should not all be specified as non-
null values.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests retrieval of
attributes conditions for all access identifiers of the type defined by the command code
modifier. Use of the command code modifier ALL results in retrieval of all attributes for
the LMS1000. If the command code modifier is ALL, the value of the access identifier
must be ALL. A NULL value is not permitted for this parameter. Invalid values received
for this parameter return an error response with the error code IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the alarm conditions being
retrieved. This parameter is an attribute of the LMS1000 channel or limit configuration.
Valid values for this parameter are as follows:
CR critical alarm
MJ major alarm
MN minor alarm
NA not alarmed
NR not reported
NULL request retrieval of alarm conditions for all of the above codes
Invalid values for this parameter return an error response with the error code IDNV.
<condtype>
Specifies the condition type parameter associated with the attributes to be retrieved.
Specifying a NULL value causes all attributes to be retrieved which match the other
bounding parameters. This parameter is an attribute of the LMS1000 channel or limit