Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-340 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
RETRIEVE-ALARM-ENVIRONMENT
(RTRV-ALM-ENV)
Referenced In: TR-NWT-000833, Issue 5; pg. 4-217
General Description: Instructs LMS1000 to send the current state of its alarm
conditions associated with the LMS1000 environment.
Related Commands: None
Related Messages: REPORT ALARM ENVIRONMENT
LMS1000 Access Level: 1
LMS1000 Equivalent: None
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter identifies equipment associated with the
environmental alarm being requested. Entering a value of ALL requests retrieval of all
environmental alarms specified by the notification code (<ntfcncde>) parameter and
alarm type (<almtype>) parameter. A NULL value is not permitted for this parameter.
Invalid values received for this parameter return an error response with the error code
IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the environmental alarm
conditions being retrieved. This parameter is an attribute of the LMS1000 channel or limit
configuration.
Valid values for this parameter are as follows:
CR critical alarm
MJ major alarm
MN minor alarm
NULL request retrieval of environmental alarm conditions for all of the above codes
Invalid values for this parameter return an error response with the error code IDNV.
<almtype>
Specifies the alarm type parameter associated with the environmental alarms being
retrieved. Specifying a NULL value requests retrieval of all types of environmental
alarms. Values are derived from the CONDITION TYPE attribute of the LMS1000
channel or limit configuration with which the alarm is associated. A value of MISC for this
attribute is not supported in LMS1000. The error code for an invalid value for this
parameter is INUP.
<almmsg>
This parameter is not supported in LMS1000.