PRCONFIG LPS
Description: Displays the current settings and equipment inventory of the LPS Power
System.
Command Level: 2
Syntax: P LP, P LP S, P LP I, P LP P, P LP D, P LP R, P LP N<#>,
P LP N<#>-<#>
Comments: The settings or equipment inventory of the LPS can be viewed separately
by entering the command P LP followed by a space and then the specifier SETTINGS or
INVENTORY.
Command<6>: p lp ?
PRCONFIG LPS Displays the LPS system adjustment settings
alarm setpoints values, and configuration
parameters and the LPS hardware equipment
inventory for all bays and the MCA node.
PRCONFIG LPS N<#> Displays only the LPS hardware equipment
inventory for the specified bay.
PRCONFIG LPS N<#>-<#> Displays only the LPS hardware equipment
inventory for valid LPS bays and the MCA
node that fall within the specified range of LMS
node numbers.
PRCONFIG LPS SETTINGS Displays only the LPS system adjustment settings
alarm setpoints values, and configuration
parameters.
PRCONFIG LPS INVENTORY Displays only the LPS hardware equipment
inventory for all bays and the MCA node.
PRCONFIG LPS PCU Displays only the LPS hardware equipment
inventory of PCUs
PRCONFIG LPS DISTRIBUTION Displays only the LPS hardware equipment
inventory of bay distribution panels.
Notes:
Low voltage disconnect settings are only displayed for installed LVDs.
In the event of a PCU failure, the inventory displayed for the failed PCU is as follows.
PCU01-No Reply
PCU02-No Reply
Subsystem shunts are only displayed if a subsystem is installed.
Related Commands: PRCONFIG, PRCONFIG VORTEX
Example:
Command<6>: p lp
LPS POWER SYSTEM SETTINGS AS OF 14:21:32 ON 12/10/03.
System Adjustment Setpoints
Description Value Units
Float Voltage 52.10 VDC